Accessible Doors and Entrances


Summary

Accessible entrances and doors need a minimum clear opening width, clear space beside the latch, low-effort hardware, limited thresholds, and slow-closing or automatic operation. Door clearances drive wall layout at every accessible room, so draw the maneuvering clearances with the door swing.


Cols

Scope

Terminology

Requirements

Entrances

Door dimensions and clearances

Operation and hardware

Automatic doors

Worked examples

Latch side clearance

A 3 ft 0 in. door opens into a 6 ft wide room, hinged on the right, approached from the corridor (pull side).

Step Requirement Result
Clear width 3 ft door at 90 degrees minus stop and hinge About 34 in., meets 32 in.
Perpendicular clearance 60 in. in front of the door on the pull side Keep 5 ft of corridor clear
Latch side clearance 18 in. beside the latch Offset the door at least 18 in. from the corner
Push side 48 in. Room depth of at least 4 ft in front of the door

Vestibule

Two doors in series open outward with a 7 ft 0 in. vestibule between them.

Step Calculation Result
Required spacing 48 in. plus the swing of any door swinging into the space 48 in. + 36 in. = 84 in.
Provided 7 ft = 84 in. Meets the minimum if one door swings into the vestibule

Public entrances

A building has five public entrances.

Step Calculation Result
Required 5 × 0.60 3 entrances
Signs Not all entrances comply Accessible entrances show the symbol; add directional signs at those that do not