IFC Fire Hydrants and Water Supply


Summary

The IFC requires an approved water supply that can deliver the fire flow a building needs, and fire hydrants within set distances of the building and along access roads. Fire flow depends on building area, construction type, and sprinklers, so it fixes the size of the water service and the hydrant layout early in site design.


Cols

Scope

Terminology

Requirements

Water supply and fire flow

Fire flow (Appendix B)

Fire-flow calculation area (sq ft) Sprinklers Minimum fire flow (gpm) Duration (hours)
0 to 3,600 None 1,000 1
3,601 and greater None Table B105.1(2) value Table B105.1(2) duration
0 to 3,600 NFPA 13D system 500 1/2
3,601 and greater NFPA 13D system 1/2 of the Table B105.1(2) value 1
Fire flow (gpm) Types II-B and III-B (sq ft) Type V-B (sq ft) Type I-A and I-B (sq ft)
1,500 0 to 5,900 0 to 3,600 0 to 22,700
2,000 7,901 to 9,800 4,801 to 6,200 30,201 to 38,700
3,000 18,401 to 21,800 11,301 to 13,400 70,901 to 83,700
4,000 33,501 to 37,900 20,601 to 23,300 128,701 to 145,900

Hydrants

Fire flow (gpm) Minimum hydrants Average spacing (ft) Maximum distance from any point on the street frontage (ft)
1,750 or less 1 500 250
1,751 to 2,250 2 450 225
2,251 to 2,750 3 450 225
2,751 to 3,250 3 400 225
3,251 to 4,000 4 350 210
4,001 to 5,000 5 300 180
5,001 to 5,500 6 300 180
5,501 to 6,000 6 250 150
6,001 to 7,000 7 250 150
7,001 or more 8, plus 1 per 1,000 gpm over 7,000 200 120

Worked examples

Warehouse fire flow

A Type II-B warehouse of 30,000 sq ft, sprinklered with an NFPA 13 system (Group S-1).

Step Source Result
Fire-flow calculation area 30,000 sq ft Used as given
Unreduced fire flow Table B105.1(2), Type II-B, 29,301 to 33,500 3,750 gpm for 3 hours
Sprinkler reduction 25 percent of 3,750 937 gpm, but not less than 1,000
Required fire flow Greater of the two 1,000 gpm
Water supply Greater of the sprinkler demand with hose stream and 1,000 gpm Set by the sprinkler design

Hydrants for a 3,000 gpm requirement

Step Source Result
Fire flow 3,000 gpm Row 2,751 to 3,250 gpm
Minimum hydrants Table C102.1 3
Average spacing 400 ft Hydrants about 400 ft apart
Maximum distance from any frontage point 225 ft No point on the street frontage more than 225 ft away
Sprinklered building NFPA 13 Spacing up by 50 percent About 600 ft spacing, if the official allows

House fire flow

A 2,800 sq ft house with an NFPA 13D system.

Step Source Result
Calculation area 2,800 sq ft, under 3,601 Small-house row
Fire flow with 13D Table B105.1(1) 500 gpm for 1/2 hour
Unsprinklered comparison Same row 1,000 gpm for 1 hour

Coordination

Common issues

Standards

Sources