IECC Commercial Lighting Power and Controls


Summary

The commercial IECC caps the lighting power a building may install, in watts per square foot by space type or for the whole building, and requires automatic controls such as occupancy sensors, time switches, and daylight responsive dimming. Lighting design is checked against both the power allowance and the control requirements, so the lighting layout, fixtures, and controls are set together.


Cols

Scope

Terminology

Requirements

Power allowance

Controls

Worked examples

Lighting allowance by area

An illustrative office floor of 10,000 sq ft with an illustrative allowance of 0.8 W per sq ft.

Step Calculation Result
Allowed power 10,000 × 0.8 8,000 W
Proposed 300 fixtures at 22 W 6,600 W
Check 6,600 against 8,000 Complies with 1,400 W to spare
Resulting LPD 6,600 ÷ 10,000 0.66 W per sq ft

Space-by-space

Space Area (sq ft) Allowed (W per sq ft) Allowed power (W)
Open office 6,000 0.7 4,200
Conference 1,000 0.9 900
Corridor 1,500 0.4 600
Lobby 500 0.9 450
Total 9,000 6,150

The values are illustrative; the code tables supply the actual allowances.

Control check

Space Control
Private office Occupancy or vacancy sensor, manual on
Corridor Occupancy sensor or time switch
Perimeter zone with windows Daylight responsive dimming
Lobby Time switch or occupancy sensor