NFPA 285 Exterior Wall Fire Propagation


Summary

NFPA 285 is a full-scale fire test of an exterior wall assembly that measures how flames spread up and across the wall, through cavities, and from floor to floor. The building code requires it for walls with combustible insulation, weather barriers, or cladding in Types I through IV construction, so the whole assembly must be selected from tested or listed designs.


Cols

Scope

Terminology

Requirements

What the test measures

Where the IBC requires it

Typical exceptions

Worked examples

Choosing a wall for a mid-rise

A 55 ft tall Type III-A building with brick veneer over foam plastic insulation, a combustible WRB, and steel studs.

Step Check Result
Construction type Type III exterior walls are noncombustible; combustible components are limited NFPA 285 applies to the assembly
Height 55 ft is over 40 ft Combustible WRB requires compliance (Section 1402.6)
Compliance path Section 1402.8 Use a listed assembly that matches every layer, or an approved analysis
Substitutions Change of insulation, WRB, or cladding Re-verify against the listing

Metal panel system

Step Check Result
Product Metal composite panels with a combustible core Test or listing required over 40 ft
Alternative Panels with a noncombustible core Different path; confirm the code section
Documentation Test report matching the assembly Submit with the wall section

Submittal checklist

Item Where it shows
Wall section with every layer and thickness Detail drawings
Listing or report number Specification and submittal
Fastening and cavity details Details and shop drawings
Fire barrier at floor edge See the perimeter fire containment detail

Coordination

Common issues

Standards

Sources