IRC Fire-Resistant Separations


Summary

The IRC sets fire protection for houses by distance to the lot line for exterior walls, by rated walls between townhouses and two-family units, by gypsum board between the garage and the dwelling, and by fireblocking in concealed spaces, with sprinklers relaxing several of them. Setbacks, garage layout, and sprinkler status decide these assemblies, so settle them with the site plan.


Cols

Scope

Terminology

Requirements

Exterior walls

Element Distance from lot line Requirement
Walls Less than 5 ft 1-hour rated (ASTM E119 or UL 263), exposed from both sides
Walls 5 ft or more Not rated
Projections Less than 2 ft Not allowed
Projections 2 ft to under 5 ft 1-hour underside, heavy timber, or fire-retardant-treated wood
Projections 5 ft or more Not rated
Openings Less than 3 ft Not allowed
Openings 3 ft to under 5 ft 25 percent of wall area maximum
Openings 5 ft or more Unlimited
Penetrations Less than 3 ft Comply with Section R302.4
Element Distance from lot line Requirement
Walls Less than 3 ft 1-hour rated, exposed from the outside
Walls 3 ft or more Not rated
Projections Less than 2 ft Not allowed
Projections 2 ft to under 3 ft 1-hour underside, heavy timber, or fire-retardant-treated wood
Projections 3 ft or more Not rated
Openings Less than 3 ft Not allowed
Openings 3 ft or more Unlimited

Townhouses and two-family dwellings

Garages

Location Protection
Garage side of the dwelling wall and ceiling 1/2 in. gypsum board
Dwelling spaces above the garage 5/8 in. Type X gypsum board
Structure supporting the separated assemblies 1/2 in. gypsum board
Garage within 3 ft of the dwelling on the same lot 1/2 in. gypsum board on the interior side of exterior walls in that area

Concealed spaces and stairs

Sprinklers

Worked examples

House near a side lot line

A house is 4 ft from the side lot line, not sprinklered.

Step Table R302.1(1) Result
Wall Under 5 ft 1-hour rated from both sides
Openings 3 ft to under 5 ft 25 percent of the wall area at most
Eaves 2 ft to under 5 ft 1-hour underside, heavy timber, or FRTW
Penetrations 3 ft or more None required

The same house sprinklered: wall not rated at 3 ft or more, unlimited openings, eaves unrated at 3 ft or more.

Garage with a bedroom above

Location Protection
Garage ceiling under the bedroom 5/8 in. Type X gypsum board
Garage wall shared with the house 1/2 in. gypsum board on the garage side
Door from the garage to the hall Solid wood or steel at least 1-3/8 in. thick, or 20-minute rated, self-closing and self-latching
Door from the garage to a bedroom Not permitted

Townhouse wall

Case Wall
Sprinklered townhouses One common wall, 1 hour
Unsprinklered townhouses One common wall, 2 hours, or two 1-hour double walls
Both Continuous to the roof deck, 30 in. parapet unless an exception applies

Coordination

Common issues

Standards

Sources