IRC Smoke and Carbon Monoxide Alarms


Summary

The IRC requires smoke alarms in every sleeping room, outside each sleeping area, and on every story, and carbon monoxide alarms outside sleeping areas and on every level of dwellings with fuel-fired appliances or an attached garage, all interconnected and hard-wired with battery backup in new work. Alarm locations, wiring, and interconnection are set on the electrical plan, so show them in the drawings rather than leaving them to the electrician.


Cols

Scope

Terminology

Requirements

Smoke alarms

Carbon monoxide alarms

Worked examples

Two-story house with attached garage

Three bedrooms upstairs off one hall, a finished basement, a gas furnace, and an attached garage opening into the house.

Location Smoke alarm CO alarm
Each of the three bedrooms Required Not required in the bedroom
Upstairs hall outside the bedrooms Required Required
First floor, living area Required Required (every occupiable level)
Basement Required (additional story) Required
Garage Not permitted Not required inside the garage
Total 6 smoke alarms 3 CO alarms

All alarms are interconnected so that one sounds all.

Alarm placement near a bath

A bathroom with a shower opens to the upstairs hall.

Step Check Result
Distance from bathroom door 3 ft horizontally Locate the hall alarm at least 3 ft from the door
Kitchen distance 20 ft from a cooking appliance Keep alarms out of the kitchen area, 10 ft allowed for certain alarm types
Supply register 36 in. horizontal path Move off the register line

Addition triggers

A 400 sq ft bedroom addition is built onto a house with a gas furnace and no existing alarms.

Step Check Result
Smoke alarms Alteration or addition Alarms located as in new dwellings throughout the unit
CO alarms Fuel-fired appliance exists Required outside the sleeping areas and on each level
Wiring Interconnect and power Hard-wired with battery backup where the structure is exposed

Coordination

Common issues

Standards