IBC Openings and Penetrations


Summary

Openings, penetrations, and joints in rated walls and floors must be protected so the assembly keeps its rating: fire doors and fire windows cover openings, firestop systems cover pipes, cables, and ducts that pass through, and joint systems cover gaps at movement joints and at the building edge. Each protection is a listed, labeled system with its own rating and test method, so the rating on the wall sets what the door, firestop, or joint must be.


Cols

Scope

Terminology

Requirements

Fire doors

Wall or barrier type Wall rating (hours) Fire door rating (hours)
Fire walls and fire barriers over 1 hour 4 3
Fire walls and fire barriers over 1 hour 3 3, or two 1-1/2 hour doors on opposite sides
Fire walls and fire barriers over 1 hour 2 1-1/2
Fire walls and fire barriers over 1 hour 1-1/2 1-1/2
Fire barriers, shafts and exit enclosures 1 1
Other fire barriers 1 3/4
Fire partitions, corridor walls 1 1/3 (20 minutes)
Fire partitions, corridor walls 1/2 1/3 (20 minutes)
Other fire partitions 1 3/4
Other fire partitions 1/2 1/3

Fire windows and glazing

Through penetrations

Membrane penetrations

Nonrated assemblies

Joints and perimeters

Worked examples

Door ratings through a floor plate

Location Wall type and rating Door rating
Corridor wall to office suite Fire partition, 1 hour 20 minutes
Interior exit stair Fire barrier, 1 hour 1 hour
Elevator hoistway enclosure Fire barrier, 2 hours 1-1/2 hours
Fire wall dividing two buildings Fire wall, 3 hours 3 hours

In a building sprinklered throughout, the stair door does not need the 450 degrees F temperature rise limit.

Pipe through a rated floor

A 4 in. plastic drain pipe passes through a 2-hour concrete floor.

Step Check Result
Penetration type Through penetration of a horizontal assembly Section 714.5.1.2
F rating At least 1 hour and at least the floor rating 2 hours
T rating At least 1 hour and at least the floor rating 2 hours, unless an exception applies
Test ASTM E814 or UL 1479 Listed firestop system for plastic pipe in concrete

Outlet boxes in a 1-hour partition

Step Check Result
Box size Steel, up to 16 sq in. Allowed
Opposite sides 24 in. horizontal separation Offset the boxes by at least 24 in.
Aggregate 100 sq in. per 100 sq ft of wall A 10 ft by 10 ft wall can hold about six 16 sq in. boxes