IBC Types of Construction


Summary

Type of construction classifies a building as Type I through V, with A and B subtypes, based on whether its structural elements are noncombustible, mass timber, or any material, and on the fire-resistance rating each element must have. It is the second code decision after occupancy, because the type sets the allowable height and area and the rating of the frame, walls, floors, and roof.


Cols

Scope

Terminology

Classification

Type definitions

Required ratings

Type Primary frame Exterior bearing walls Interior bearing walls Floor Roof
I-A 3 3 3 2 1-1/2
I-B 2 2 2 2 1
II-A 1 1 1 1 1
II-B 0 0 0 0 0
III-A 1 2 1 1 1
III-B 0 2 0 0 0
IV-A 3 3 3 2 1-1/2
IV-B 2 2 2 2 1
IV-C 2 2 2 2 1
IV-HT HT 2 1 or HT HT HT
V-A 1 1 1 1 1
V-B 0 0 0 0 0

Combustibles in Types I and II

Worked examples

Choosing a type for a four-story office

Group B, four stories above grade, about 52 ft tall, 15,000 sq ft per floor, sprinklered throughout (IBC 2024 Tables 504.3, 504.4, and 506.2).

Type Stories allowed (sprinklered) Height allowed (sprinklered) Area per story (sprinklered, multi-story) Result
II-B 4 75 ft 69,000 sq ft Allowed; no structural ratings
V-A 4 70 ft 54,000 sq ft Allowed; 1-hour frame, walls, floors, roof
V-B 3 60 ft 27,000 sq ft Not allowed; fourth story exceeds 3

Type II-B uses noncombustible framing with no rating and is permitted without reductions. Type V-A allows wood framing but requires 1-hour protection on the frame, bearing walls, floors, and roof, which usually means added gypsum board.

Roof framing in an unrated type

Group B, Type II-A, roof deck 28 ft above the second floor below.

Step Check Result
Group B, not F-1, H, M, or S-1 20 ft rule available
Roof height 28 ft above the highest floor below Exceeds 20 ft
Roof members Table 601 requires 1 hour for II-A roof No fire protection needed on roof members

Coordination

Common issues

Standards