IFC Hazardous Materials


Summary

The IFC limits how much of each hazardous material a building may hold in a control area, based on a table of maximum allowable quantities that rises with sprinklers and approved cabinets, and requires fire-rated construction and signs when quantities approach the limits. Laboratories, workshops, retail, and storage all hold hazardous materials, so identify the quantities in the program early to avoid being classified as a high-hazard occupancy.


Cols

Scope

Terminology

Requirements

Control areas and quantities

Construction and separation

Systems, signs, and release

Worked examples

Sprinkler and cabinet increases

A chemistry lab stores a flammable liquid with a table MAQ of 120 gallons per control area (illustrative value).

Step Footnote Result
Table MAQ Base 120 gallons
Sprinklered building Note d, add 100 percent 240 gallons
Approved storage cabinets Note e, add 100 percent 240 gallons for cabinet storage alone
Both Cumulative, add 100 + 100 percent 360 gallons

Control areas on a floor

A three-story lab building needs 600 gallons of the same liquid.

Step Calculation Result
MAQ with sprinklers and cabinets 360 gallons per control area From above
Control areas needed 600 ÷ 360 1.7, so 2 control areas
Separation Fire barriers and horizontal assemblies per Table 5003.8.3.2 Rated enclosures between control areas
Floor assemblies Section 5003.8.3.4 2 hour floors, 1 hour exception
Table limit on control areas per story Table 5003.8.3.2 Check the percentage of MAQ allowed per story and floor

High-rise limit

A laboratory on the 12th floor of a sprinklered building.

Step Calculation Result
Above the 10th story 5 percent of MAQ 120 × 0.05 = 6 gallons
Sprinklered Add 100 percent 12 gallons

Coordination

Common issues

Standards