NFPA 80 Fire Doors and Opening Protectives


Summary

NFPA 80 governs how fire door assemblies are installed, field modified, inspected, and maintained, including the gaps allowed around the door, the hardware that may be used, and what may be done in the field. Door gaps, hardware, and field cutting are common failures at inspection, so the architect's door and hardware schedules must match the labeled assemblies.


Cols

Scope

Terminology

Requirements

Clearances

Field modification and glazing

Inspection

Where the IBC requires it

Worked examples

Clearance check on a hollow metal pair

A pair of hollow metal doors in a 1-hour wall.

Location Limit Field measurement Result
Head 1/8 in. plus or minus 1/16 in. (up to 3/16 in.) 3/16 in. Within the limit
Meeting stiles Same 1/4 in. Exceeds; adjust the leaves
Bottom 3/4 in. maximum 5/8 in. Within the limit

Wood door undercut

A 1-1/2 hour wood door is too long for a thick carpet.

Step Check Result
Maximum bottom clearance 3/4 in. from the finished floor Door may be raised to 3/4 in.
Field undercutting Wood doors up to 3/4 in. after checking with the manufacturer Allowed
Carpet thickness Measure to the top of the finished floor Use the floor surface, not the subfloor

Vision light in a new wood door

Step Edition Result
Ordering today Code references an earlier edition Glazing by the factory or under label service
After a code adopting 2025 Section 4.4.4.4 Field install a labeled metal kit in a cutout made at the factory or shop

Coordination

Common issues

Standards

Sources