IBC Means of Egress


Summary

The means of egress is the continuous, unobstructed path from any occupied point in a building to a public way, made up of the exit access, the exit, and the exit discharge. It is the first code check on every plan, because occupant load drives the number of exits, door and stair widths, travel distance, and corridor layout.


Cols

Scope

Terminology

Design sequence

Work in this order: occupant load, number of exits, separation, width, travel distance, corridors, stairs, then doors and the path. Each step feeds the next.

Occupant load

Use Load factor (sq ft per occupant)
Assembly, standing space 5 net
Assembly, concentrated (chairs only) 7 net
Assembly, unconcentrated (tables and chairs) 15 net
Educational, classroom 20 net
Educational, shops and vocational 50 net
Exercise rooms 50 gross
Mercantile 60 gross
Business areas 150 gross
Residential 200 gross
Commercial kitchens 200 gross
Parking garages 200 gross
Warehouses 500 gross

Where a function is not listed, the building official assigns a factor.

Number of exits

Group Max occupant load, one exit Max common path, no sprinklers (ft) Max common path, sprinklered (ft)
A, E, M 49 75 75
B 49 100 (load 30 or less), 75 (load over 30) 100
R-2 20 Not permitted 125

Exit separation

Egress width

Component Standard Sprinklered with voice alarm
Stairways (Section 1005.3.1) 0.3 in. per occupant 0.2 in.
Other components: doors, corridors, ramps (Section 1005.3.2) 0.2 in. per occupant 0.15 in.

Exit access travel distance

Group No sprinklers (ft) Sprinklered (ft)
A, E, F-1, M, R, S-1 200 250
B 200 300
F-2, S-2, U 300 400
I-4 150 200

Corridors

Stairs

Doors and the path itself

Worked examples

Single-story office

Group B, one story, 150 ft by 80 ft, 12,000 sq ft gross, sprinklered throughout (Section 903.3.1.1).

Step Calculation Result
Occupant load 12,000 ÷ 150 gross 80 occupants
Number of exits 80 exceeds 49 2 exits
Exit separation Diagonal = √(150² + 80²) = 170 ft; one-third 56 ft 8 in. minimum apart
Egress width 80 × 0.2 in. = 16 in. 32 in. door minimum governs
Travel distance Table 1017.2, Group B sprinklered 300 ft; the plan's longest run is well under
Corridor 80 occupants 44 in. minimum (36 in. only under 50 occupants); no rating needed

Without sprinklers, separation grows to 85 ft (half the diagonal), travel distance drops to 200 ft, and corridors serving more than 30 become 1-hour rated.

Three-story office stair

Group B, three stories, 30,000 sq ft gross per story, sprinklered with a voice alarm system.

Step Calculation Result
Occupant load per story 30,000 ÷ 150 200 occupants (stories are not added)
Stair width required, standard 200 × 0.3 in. 60 in. total
Stair width required, reduced 200 × 0.2 in. 40 in. total
Exits per story 200 is 500 or fewer 2 stairs
Stair width provided Two stairs at the 44 in. minimum 88 in. total; the 44 in. minimum governs even with the reduction

Loss of one stair still leaves 44 in., above the 50 percent minimum of 30 in. (standard factor) or 20 in. (reduced factor).