IFC Fire Apparatus Access Roads


Summary

Fire apparatus access roads give fire trucks a paved, unobstructed route to within a set distance of the building, with minimum width, overhead clearance, turnarounds at dead ends, and added aerial access for taller buildings. Access roads decide the site plan, drive aisles, and building position, so locate them on the first site layout.


Cols

Scope

Terminology

Requirements

Where required

Dimensions

Appendix D (where adopted)

Length (ft) Width (ft) Turnaround
0 to 150 20 None
151 to 500 20 120 ft hammerhead, 60 ft "Y," or 96 ft diameter cul-de-sac
501 to 750 26 Same options
Over 750 Special approval Special approval

Marking, obstruction, and gates

Worked examples

Reach to a warehouse

A 300 ft by 200 ft warehouse sits on a lot with a road along one long side.

Step Check Result
Distance 150 ft from all portions of the first-story walls Road along the long side reaches walls within 150 ft only for that side
Far side Distance from the road to the far long wall About 200 ft, over 150 ft
Fix Add access around the building or request an increase for a sprinklered building Loop road or the sprinklered-building exception

Dead-end drive

A 400 ft dead-end fire lane serves a building (Appendix D adopted).

Step Check Result
Length band 151 to 500 ft 20 ft width required
Turnaround Table D103.4 120 ft hammerhead, 60 ft "Y," or 96 ft cul-de-sac
Hydrant on the road D103.1 Widen to 26 ft

Aerial access

A four-story building with a roof 48 ft above grade.

Step Check Result
Roof height 48 ft exceeds 30 ft Aerial road required (if Appendix D is adopted)
Width 26 ft Provide 26 ft clear
Position 15 ft to 30 ft from the building, parallel to one side Place the road along the main facade
Overhead lines None over the road or between it and the building Relocate utilities or trees